The Side Effect Nobody Mentions at Installation

This is a genuine consequence of doing the right thing, and it catches buildings out months after the work.

Key point

Fitting a backflow preventer turns a building into a closed system, because water can no longer expand back toward the main. EPA’s manual records a case where thermal expansion in that closed system generated dangerous backpressure, and notes that closed systems require pressure relief.

Source: U.S. EPA, Cross-Connection Control Manual, EPA 816-R-03-002, February 2003.

CrossConnect is a referral service, not a contractor. We connect property owners and managers with independent contractors. Backflow assembly testing is normally restricted to testers holding a specific certification and using calibrated equipment, and the report usually has to reach your water purveyor — ask to see the certification and ask who files the report. We carry out no testing, we certify nobody, we do not set prices, and we never charge callers anything. Nothing here selects a device for any installation or states that any assembly is passing.

What changes on the day it is fitted

Before: water in a building could move slightly back toward the main as it expanded. After: it cannot, because that is precisely what the assembly exists to prevent.

The building has become a closed system. Nothing has gone wrong; the device is doing exactly its job.

Why that matters

Water expands as it is heated and it does not compress. In an open system that expansion is absorbed by the supply. In a closed one it has nowhere to go, so it raises pressure instead.

EPA’s manual carries a case in which installing a backflow preventer created a closed system and thermal expansion in solar heating tanks generated dangerous backpressure, and notes that closed systems require pressure relief.

Source: U.S. EPA, Cross-Connection Control Manual, EPA 816-R-03-002, February 2003.

What it looks like in a building

Pressure that climbs when nothing is being drawn and falls back as soon as a tap is opened. A relief valve that weeps or discharges with no obvious fault. Fittings and flexible connectors failing earlier than they should. Occasional noise as pressure releases.

All of it is easy to blame on the plumbing, and the cause is a change made at the service connection.

What to raise, and when

Ask before the assembly goes in whether the building will be a closed system afterwards and how expansion is going to be accommodated. Asking afterwards is a second visit.

It is also worth raising at any change that adds a check valve, a pressure reducing valve or a meter with one built in, because those create the same condition without anybody calling it backflow prevention.

What this page is not

It is not advice about your water heater settings, and this site states no temperature for anything. The subject here is pressure in a closed system, which is a different quantity with a different remedy.

If a relief device on a heating appliance is discharging, that is a question for a contractor at the appliance, not a website.

Know what is on the tag before you call.Make, model, size and the date of the last test are usually stamped or tagged on the assembly itself, and they decide which test kit and which paperwork the visit needs. We will route you to somebody who covers your area, selected on the ZIP code of the property, and you are never charged. Backflow is our specialty, though the number will take any plumbing request on the property.